Configuring LOGO! 0BA7/0BA8

To enable communication to LOGO! 0BA7 TCP/IP you must first set up the PLC IP address and add a server connection. Follow the next steps in LOGO!Soft Comfort (V8):

  • Select the menu item Tools > Ethernet Connections
  • Right-click on Ethernet Connections and select Add server connection
  • Double-click on the newly created connection to edit settings
  • Check Connect with an Operator Panel and Accept all connection requests
  • Type the value: 02.00 in TSAP field
  • Load the program into the PLC